Specification

Specifications table for model AKS1202
ItemPerformance characteristics
Rated Voltage24 V DC
Operating Voltage Range 90 to 110 %V of rated voltage (21.6 to 26.4 V DC)
Inrush Current12 A or less
Current Consumption200 mA or less
Allowed Momentary Power Off Time10 ms
FuseBuilt-in type
Terminal Screw M2
Ambient Temperature0 to 55 degrees
Storage Temperature-20 to +75 degrees
Ambient Humidity30 to 85 % RH (at 20 degrees , non-condensing)
Breakdown Voltage (Initial)500 V AC 1 minute, RS485 terminals ⇔ Combined power and ground terminals
Insulation Resistance (Initial) 100 Mohm or higher (500 V DC using an insulation resistance meter), RS485 terminals ⇔ Combined power and ground terminals
Vibration Resistance10 to 55 Hz, 1 cycle / min.: double amplitude of 0.75 mm, 1 hour on 3 axes
Shock Resistance294 m / s2 or more, 5 times on 3 axes
Dimensions25 x 60 x 90
Weight (Typ.)Approx. 80 g
EthernetInterface: IEEE802.3u, 10BASE-T / 100BASE-TX
Connector shape: RJ45
Transmission specifications (Transmission speed): 10 Mbps / 100 Mbps
Transmission specifications (Transmission method): Base band
Transmission specifications (Max. segment length): 100 m
Communication cable: Category 5 UTP cable
Protocol: Modbus TCP(RTU, ASCII), TCP / IP
Functions: Auto negotiation function, MDI / MDI-X, Auto crossover function
RS232CInterface: RS-232C (non-insulated)
Conversion COM port: COM1 (Note)
Communication style: 1: 1 communication
Number of connection units: 1 unit
Communication method: Full duplex system
Synchronous system: Synchronous communication method
Transmission distance: 15 m 49 ft
Transmission speed: 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
Connection connector quantity: Max. 3
COM receive time out: Setting range 10 ms to 300 s
Non-transmission connection cut-off time: Setting range: 0 to 1800 s (Setting value of 0 is not cut off)
Transmission format (Data length): 8 bit fixed
Transmission format (Parity): Odd / even / none
Transmission format (Stop bit): 1 bit / 2 bit
Transmission format (End code): CR / CR+LF / None
Serial ⇔ Ethernet conversion format: Command response format
(Note) COM1 and COM2 can be used simultaneously.
RS485Interface: RS-485 (insulated)
Conversion COM port: COM2 (Note 1)
Communication style: 1: N communication
Number of connection units: Max. 99 units
Communication method: Half-duplex operation
Synchronous system: Synchronous communication method
Transmission distance:Max. 1,200 m 3,937 ft (Note 2)(Note 3)
Transmission speed: 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
Connection connector quantity: Max. 3
COM reception time-out: Setting range 10 ms to 300 s
Non-transmission connection cut-off time: Setting range: 0 to 1800 s (Setting value of 0 is not cut off)
Transmission format (Data length): 8 bit fixed
Transmission format (Parity): Odd / even / none
Transmission format (Stop bit): 1 bit / 2 bit
Transmission format (End code): CR / CR+LF / None
Serial ⇔ Ethernet conversion format: Command response format
(Note 1) COM1 and COM2 can be used simultaneously.
(Note 2) When connecting a commercially available device, please confirm operation using the actual device. In some case, the number of stations, transmission distance, and communication speed vary depending on the connected device.
(Note 3) The values for the transmission distance, communication speed and number of stations should be within the values noted in the graph.