The NA2-N Series General Purpose And Slim Body Area Sensor offers high performance in a General-Purpose Area Sensor. The slim body (3mm thick and 30mm wide) can be installed almost anywhere. With a wide range of sensing height from 140mm (8 beam channels) to 540mm (28 beam channels), this Area Sensor is versatile for many applications.
Characteristics
6 Types Of Sensing Height Available (140mm To 540mm)
8, 24 And 28 Beam Channel Models Available In Addition To The Current Models
Interference Prevention For Parallel Installation
Selectable Lighting Pattern
Fast Response Speed (10ms Or Less)
NPN And PNP Type Available
Slim Body (13mm Thick And 30mm Wide)
Clearly Visible Wide Job Indicator
CE Marked, Conforms To EMC Directive, UL Pending
Accessories
Sensor Supporting Brackets
Sensor Mounting Brackets
Slit Masks
4-Core Cable, 3m Long
General Purpose & Slim Body Area Sensor NA2-N
Part number list
Results 24
Models table for series General Purpose & Slim Body Area Sensor NA2-N
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.7 W or less
0.6 W or less
0.7 W or less
0.6 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 2 V or less (at 100 mA source current), 1 V or less (at 16 mA source current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
1.0 W or less
0.9 W or less
1.0 W or less
0.9 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
1.0 W or less
0.9 W or less
1.0 W or less
0.9 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 2 V or less (at 100 mA source current), 1 V or less (at 16 mA source current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.7 W or less
0.6 W or less
0.7 W or less
0.6 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.8 W or less
0.7 W or less
0.8 W or less
0.7 W or less
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 2 V or less (at 100 mA source current), 1 V or less (at 16 mA source current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
1.0 W or less
0.9 W or less
1.0 W or less
0.9 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
1.0 W or less
0.9 W or less
1.0 W or less
0.9 W or less
NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)
dia. 30 mm dia. 1.181 in or more opaque object (completely beam interrupted objects)
12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less
0.9 W or less
0.8 W or less
0.9 W or less
0.8 W or less
PNP open-collector transistor - Maximum source current: 100 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 2 V or less (at 100 mA source current), 1 V or less (at 16 mA source current)
DC-12 or DC-13
ON when all beam channels are received (OFF when one or more beam channels are interrupted)
Incorporated
10 ms or less (12 ms or less when the interference prevention function is used)
Operation indicator: Red LED (lights up when one or more beam channels are interrupted) Stable incident beam indicator: Green LED (lights up when all beam channels are stably received) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch) * When an excess current flows through the output, the stable incident beam indicator and the operation indicator on the receiver blink simultaneously due to operation of the short-circuit protection circuit.
Emitting indicator: Green LED x 2 (light up during emission; one LED lights up for Frequency A setting, both LEDs light up for Frequency B setting) Job indicator: Red LED (lights up, blinks or lights off when the job indicator input is applied, selected by operation mode switch)
Incorporated
Incorporated
3 (Industrial environment)
IP40(IEC)
-10 to +55 degrees +14 to +131 degrees Fahrenheit (No dew condensation or icing allowed), Storage: -10 to +60 degrees +14 to +140 degrees Fahrenheit
35 to 85 % RH, Storage: 35 to 85 % RH
Incandescent light: 3,000 lx or less at the light-receiving face
1,000 V AC for one min. between all supply terminals connected together and enclosure
20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure
10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude in X, Y and Z directions for two hours each
500 m/s2 acceleration (50 G approx.) in X, Y and Z directions three times each
Infrared LED (Peak emission wavelength: 870 nm 0.034 mil, modulated) (Note:Peak emission wavelength has been changed from production in March, 2017.)