These products feature key-based operation for worker protection in larger areas that could be hazardous. The SG-B2 Series Safety Door Switch and the SG-D1 Series Key Selector Switch can be used in tandem to add multiple layers of protection.
Characteristics
One Key Operates Both Series
Prevents Workers From Getting Trapped
Safety door switch with key SG-B2
Part number list
Results 15
Models table for series Safety door switch with key SG-B2
Part No.
Datasheet
Contact Arrangement
Cable Length
Key Removal Position
Applicable Standards
Applicable Standards: Standards For Use
Applicable Directives
Operating Condition: Ambient Temperature
Operating Condition: Ambient Humidity
Operating Condition: Pollution Degree S
Operating Condition: Altitude
Impulse Withstand Voltage (Uimp)
Rated Insulation Voltage (Ui)
Thermal Current (Ith)
Rated Operational Voltage (Ue)/Rated Operational Current (Le)
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in
EN 1088, IEC 60947-5-1, EN 60947-5-1, GS-ET-19, UL 508, CSA C22.2 No.14
IEC 60204-1, EN 60204-1
Machinery directive (2006/42/EC) Low voltage directive (2006/95/EC)
-25 to +70 ℃ -13 to +158 ℉ (No dew condensation or icing allowed) Storage : -40 to +80 ℃ -40 to +176 ℉
45 to 85 % RH
3 (Inside 2)
2,000 m 6,561.68 ft max.
2.5 kV
250 V (Note): Ratings approved by UL, c-UL : 125 V
・2.5 A ・Ambient temperature : -25 to +60 ℃ -13 to +140 ℉ : 2.5 A max. +60 to +65 ℃ +140 to +149 ℉ : 1.5 A max. +65 to +70 ℃ +149 to +158 ℉ : 1.0 A max.
Ue
30V
125V
250V
Ie
AC
Resistive load (AC-12)
-
2.5A
1.5A
Inductive load (AC-15)
-
1.5A
0.75A
DC
Resistive load (DC-12)
2.5A
1.1A
0.55A
Inductive load (DC-13)
2.3A
0.55A
0.27A
900 operations/hour
0.05 to 1.0 m/sec.
2,000,000 (ISO 13849-1 Annex C Table C.1)
1,000,000 operations min. (GS-ET-19) Rear unlocking button : 3,000 operations min. (Type SG-B2-□-L5)
100,000 operations min. (AC-12, 250 V 1 A) 1,000,000 operations min. (AC/DC 24 V 100 mA) (900 operations/hour)
Class II (IEC 61140)(Note), 回(double-insulated) (Note): Basic insulation of 2.5 kV impulse withstand voltage is ensured between different contact circuits. When both SELV (safety extra low voltage) or PELV (protective extra low voltage) circuits and other circuits (such as 230 V AC circuits) are used for the solenoid power and contact circuits at the same time, the SELV or PELV requirements are not met any more.
1,400 N min. (GS-ET-19)(Note) (500 N min. : SG-K24 actuator) (Note): The actuator locking strength is rated at 1,400 N of static load. Do not apply a load higher than the rated value. When a higher load is expected to work on the actuator, provide an additional system consisting of another safety switch without lock (such as the SG-A1 safety switch) or a sensor to detect door opening and stop the machine.
11 mm 0.433 in min. (actuator : SG-K21) 12 mm 0.472 in min. (for other actuators)
80 N min.
700 mΩ max. (initial value, 5 m 16.404 ft cable)
IP 65 (IEC 60529)
Malfunction : 100 m/s2, Destruction : 1,000 m/s2
Malfunction : 10 to 55 Hz, half amplitude 0.35 mm 0.014 in Destruction : 30 Hz, half amplitude 1.5 mm 0.059 in