Specification

Specifications table for model AFPXHC14TD
ItemPerformance characteristics
Operating Temperature0 to +55 ℃ +32 to +131 ℉
Operating Humidity10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing)
Insulation Resistance (Test Voltage: 500 V DC)Between power supply terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter)
Between power supply terminal and service power supply terminal : 100 MΩ or more (500 V DC using an insulation resistance meter)
Between input terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter)
Between output terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter)
Vibration Resistance5 to 8.4 Hz, 3.5 mm 0.138 in single amplitude
8.4 to 150 Hz, Acceleration 9.8 m/s2
10 min. each in the X, Y and Z directions (1 octave/min)
Shock Resistance147 m/s2, 4 times each in the X, Y and Z directions
Operating Environment No corrosive gas and no excessive dust
Noise Immunity1,000 V [P-P] with pulse widths of 50 ns and 1 μs (using a noise simulator) (Power supply terminal)
Overvoltage ClassCategory II
Pollution Level 2
Storage Ambient Temperature-40 to +70 ℃ -40 to +158 ℉
Storage Ambient Humidity10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing)
Breakdown voltage : Transistor outputDC power supply
Between power supply terminal and earth terminal : 500 V AC for 1 minute
Between power supply terminal and service power supply terminal : -
Between input terminal and earth terminal : 500 V AC for 1 minute
Between output terminal and earth terminal : 500 V AC for 1 minute
(Note) : Cut-off current 5 mA (Initial value at shipment)
Applicable standard for EC directivesEMC directive: EN 61131-2 (directive concerning emission, immunity and low voltage)
Programming MethodRelay symbol
Control methodCyclic operation
Program MemoryBuilt-in Flash ROM
Program Capacity16 k steps
High-level instructionsApprox. 220
Basic instructionsApprox. 110
Operation Speed [Basic instruction (ST)]
Approx. 0.04 μs/step (under 7 k steps)
Approx. 0.7 μs/step (7 k steps or more)
[High-level instruction (F0MV)]
Approx. 0.22 μs/step (under 7 k steps)
Approx. 1.73 μs/step (7 k steps or more)
Operation memory : Link relay : External input (X)1,760 points (X0 to X109F)
(Note) : The number of points in the table is the number of points of operation memory. The number of points actually available to be used is determined by the hardware configuration.
Operation memory : Link relay : External output (Y)1,760 points (Y0 to Y109F)
(Note) : The number of points in the table is the number of points of operation memory. The number of points actually available to be used is determined by the hardware configuration.
Operation memory : Link relay : Internal relay (R)Default: 8,192 points (R0 to R511F)
FP-X compatible specifications: 4,096 points
(Note) : Can be selected by the setting of the system register No. 1 (internal relay capacity). To provide compatibility with the conventional FP-X series control unit, select 4,096 points.
Operation memory : Link relay : Special internal relay (R)240 points
Operation memory : Link relay : Timer / Counter (T / C)1,024 points (Initial settings Timer: 1,008 points, Counter: 16 points)
(Note) : The number of timer points can be changed by the setting of the system register No.5.
Operation memory : Link relay : Link relay (L)2,048 points (L0 to L127F)
Operation Memory: Memory Area: Data Register (DT)12 k words
Operation Memory: Memory Area: Special Data Register (DT)500 words
Operation Memory: Memory Area: Link Data Register (LD)256 words (LD0 to LD255)
Operation Memory: Memory Area: Index Register (A)14 words (I0 to ID)
Operation memory : Memory area : File register (FL)None
Differential PointsPoints for program capacity
Master Control Relay Points (MCR) 256 points
Number of labels (JMP + LOOP)256 points
Number of Step Ladders1,000 steps
Number of Subroutines 500 subroutines
Number of Interrupt Program Input 8, Constant 1
High-speed counter : Control unit inputSingle-phase 8 channels (100 kHz × 4, 10 kHz × 4) or 2-phase 4 channels (50 kHz × 2, 10 kHz × 2)
(Note 1) : The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used.
(Note 2) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication.
High-speed counter : Pulse I/O with cassette installedInstallation not possible
Pulse output / PWM output : Control unit output3 channels
[Pulse output]
each 100 kHz
[PWM output]
3 channels
1 Hz to 70 kHz (Resolution of 1000)
70.001 kHz to 100 kHz (Resolution of 100)
(Note 1) : The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used.
(Note 2) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication.
Periodical Interrupt 0.1 ms to 30 sec.
(Note) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication.
Pulse Catch Input<br>Interrupt Input8 points (Control unit input: 8 points)
(Note) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication.
Potentiometer input1 channel (0 to 4,000)
Input time constant processingAvailable
Clock / calendarAvailable (only when the master memory cassette AFPX-MRTC and battery are installed)
h ROM backup : Backup by F12 / P13 instructionsAll area of Data register
h ROM backup : Automatic backup when power is offCounter: 16 points, Internal relay: 128 points,
Data register: 315 words
Battery backupMemory set in hold area of system register
(only when battery is installed)
Battery lifetime5 years or more in the actual use condition (operating 8 hours a day)
(Note) : Battery lifetime values is calculated when the power is not completely turned on. Since the actual value depends on conditions of use, in practice, the lifetime may be shorter.
PasswordYes (Can be selected from 4 digits, 8 digits or 32 digits)
Self-diagnostic functionWatchdog timer, program syntax check, etc.
PLC link functionMax. 16 units, link relay: 1,024 points, link register: 128 words
(Data transfer, remote programming: Not available)
Rewriting in RUN modeAvailable (downloading in RUN mode, program rewriting in RUN mode)
(Max. 512 steps)

Stock Check

Important

The service is owned, operated, controlled and managed by Panasonic's distributors.

For pricing, delivery and technical questions related to this service, please direct to them.

Panasonic assumes no responsibility for any dealings you may have with distributors.