Specifications
| Item | Performance characteristics |
|---|---|
| Rated Coil Voltage | 24 V DC |
| Contact Arrangement | 1 Form A |
| Protective Construction | Flux-resistant |
| Operating Function | Single side stable |
| Terminal Type | PC board terminal |
| Contact Type | Standard type |
| Packing Quantity; Inner Carton (Pcs.) | 25 |
| Packing Quantity; Outer Carton (Pcs.) | 100 |
| Operate Voltage (@20oC) | Max. 75% V of rated coil voltage (Initial) |
| Release Voltage (at20°C) | Min. 5% V of rated coil voltage (Initial) |
| Rated Operating Current [±10%] (at 20°C) | 80 mA |
| Resistance [±10%] (at 20°C) | 300 Ω |
| Rated Operating Power | 1,920 mW Holding: 310 mW |
| Max. Allowable Voltage | (at 55℃) 110% V of rated coil voltage |
| Contact Shape | Single |
| Contact Resistance (Initial) | Max. 10 mΩ (by voltage drop 6 V DC 20 A) |
| Contact Material | AgNi type |
| Contact rating (Inductive load) | 90 A 277 V AC cosφ = 0.8 |
| Contact Rating (Resistive Load) | 60 A 490 V AC, 55 A 800 V AC, 90 A 60 V DC |
| Max. Switching Power (Resistive Load) | 44,000 VA, 5,400 W |
| Max. Switching Voltage | 800 V AC, 60 V DC |
| Max. Switching Current | 90 A |
| Max. switching current (Inductive load) | 90 A |
| Max. carrying current | 110 A |
| Min. Switching Load (Reference Value) | 100 mA 5 V DC |
| Insulation Resistance (Initial) | Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength) |
| Dielectric Strength (Initial): Between Open Contacts | Between open Form A contacts: 2,000 Vrms for 1min (detection current: 10 mA) Between open Form B contacts: 1,000 Vrms for 1min (detection current: 10 mA) |
| Dielectric Strength (Initial): Between Contact and Coil | Between Form A contact and coil: 5,000 Vrms for 1min (detection current: 10 mA) Between Form B contact and coil: 2,000 Vrms for 1min (detection current: 10 mA) |
| Dielectric Strength: Between Form A Contact and Form B Contact | 5,000 Vrms for 1min (detection current: 10 mA) |
| Surge Withstand Voltage (Initial): Between Contact and Coil | 10,000 V (Between Form A contact and coil) 2,500 V (Between Form B contact and coil) |
| Coil Holding Voltage | 40 to 110% V (at -40 to +55℃), 40 to 60% V (at +55 to +85℃) |
| Operate Time (Initial) (At 20oC) | Max. 30 ms at rated coil voltage (without bounce) |
| Release Time (Initial) (at 20°C) | Max. 10 ms at rated coil voltage (without bounce, without diode) |
| Hock Resistance (Functional) | 98 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs) |
| Hock Resistance (Destructive) | 980 m/s2 (half-sine shock pulse: 6 ms) |
| Vibration Resistance (Functional) | 10 to 55 Hz (at double amplitude of 1.0 mm, detection time: 10 μs) |
| Vibration Resistance (Destructive) | 10 to 55 Hz (at double amplitude of 1.5 mm) |
| Mechanical Life | Min. 106 ope. (switching frequency: at 180 times/min) |
| Conditions | Ambient temperature: -40 to +55℃ (When applied coil hold voltage is 40 to 110 % V of rated coil voltage.) Ambient temperature: -40 to +85℃ (When applied coil hold voltage is 40 to 60 % V of rated coil voltage or storage.) Humidity: 5 to 85% RH (Avoid icing and condensation) |
| Weight (Typ.) | Approx. 80g |
| Inductive Load | [Switching capacity] 90 A 277 V AC cosφ = 0.8 [Number of operations] Min. 103 ope. (ON : OFF = 1 s : 9 s, at 85℃) |
| Resistive Load | [Switching capacity] 60 A 490 V AC [Number of operations] Min. 10x103 ope. (ON:OFF = 1s:9s) [Switching capacity] 55 A 800 V AC [Number of operations] Min. 103 ope. (ON:OFF = 1s:9s) [Switching capacity] 40 A 600 V AC [Number of operations] Min. 50x103 ope. (ON:OFF = 1s:9s, 85℃) [Switching capacity] 30 A 800 V AC [Number of operations] Min. 50x103 ope. (ON:OFF = 1s:9s, 85℃) [Switching capacity] 90 A 60 V DC [Number of operations] Min. 10x103 ope. (ON:OFF = 1s:9s, 85℃) |