Specifications
Item | Performance characteristics |
---|---|
Operating Function | Single side stable |
Rated Coil Voltage | 24 V DC |
Contact Arrangement | 4 Form A |
Protective Construction | Flux-resistant |
Terminal Type | PC board terminal |
Packing Quantity | Carton |
Packing Quantity; Inner Carton (Pcs.) | 10 |
Packing Quantity; Outer Carton (Pcs.) | 50 |
Operate Voltage (@20oC) | Max. 75% V of rated coil voltage (Initial) |
Release Voltage (at20°C) | Min. 5% V of rated coil voltage (Initial) |
Rated Operating Current [±10%] (at 20°C) | 167 mA |
Resistance [±10%] (at 20°C) | 144.0 Ω |
Rated Operating Power | 4,000 mW Holding: 490 mW |
Max. Allowable Voltage | (at 55℃) 110% V of rated coil voltage |
Contact Resistance (Initial) | Max. 10 mΩ (by voltage drop 6 V DC 20 A after 3 min.) Max. 3 mΩ (by voltage drop 6 V DC 50 A, reference value) |
Contact Material | AgSnO2 type |
Contact Rating (Resistive Load) | 40 A 480 V AC |
Max. Switching Power (Resistive Load) | 19,200 VA |
Max. Switching Voltage | 480 V AC |
Max. Switching Current | 50 A |
Min. Switching Load (Reference Value) | 100 mA 24 V DC |
Insulation Resistance (Initial) | Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength) |
Dielectric Strength: Between Form A Contact and Form B Contact | 5,000 Vrms for 1min (detection current: 10 mA) |
Surge Withstand Voltage (Initial): Between Contact and Coil | 10,000 V (Between Form A contact and coil) |
Coil Holding Voltage | 35 to 110% V (at -40 to +55℃, Form A contact: 50 A) 35 to 50% V (at -40 to +85℃, Form A contact: 40 A to 50 A) |
Operate Time (Initial) (At 20oC) | Max. 50 ms at rated coil voltage (without bounce) |
Release Time (Initial) (at 20°C) | Max. 30 ms at rated coil voltage (without bounce, without diode) |
Hock Resistance (Functional) | 25 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs) |
Hock Resistance (Destructive) | 980 m/s2 (half-sine shock pulse: 6 ms) |
Vibration Resistance (Functional) | 10 to 55 Hz (at double amplitude of 0.3 mm, detection time: 10 μs) |
Vibration Resistance (Destructive) | 10 to 55 Hz (at double amplitude of 1.5 mm) |
Mechanical Life | Min. 100x103 ope. (switching frequency: at 180 times/min) |
Conditions | Ambient temperature: -40 to +55℃ (When applied coil hold voltage is 35 to 110 % V of rated coil voltage.) Ambient temperature: -40 to +85℃ (When applied coil hold voltage is 35 to 50 % V of rated coil voltage or storage.) Humidity: 5 to 85% RH (Avoid icing and condensation) |
Weight (Typ.) | Approx. 180g |
Resistive Load | [switching frequency ON : OFF = 1 s : 9 s] Min. 30x103 ope. 40 A 480 V AC Min. 50x103 ope. 32 A 277 V AC |
Stock check
AHER3192
Latest Videos