Specifications
Item | Performance characteristics |
---|---|
Applicable Connector | SL-CP1 |
Supply Voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less |
Current Consumption | 50 mA or less (for the unit itself), 135 mA or less (including the sensor input current when all outputs of sensors are ON) |
Output | Relay contact 1a - Switching capacity: 30 V 1 A DC (resistive load) - Min. applied load: 10 mV 10 μA DC - Electrical lifetime: 100,000 switching operations or more (rated load, switching frequency 20 operations/min.) - Mechanical lifetime: 50 million switching operations or more (switching frequency 180 operations/min.) |
Output: Output Operation | The output relay is ON when the input signal from the sensor is ON Note : Even with only one leak detection sensor connected, an OFF signal is output if the sensor detects liquid leakage, or if the unit has been installed incorrectly. |
Response Time | 5 ms or less (excluding the response time of the sensor) |
Input No. | 8 Nos. |
Indicators: Normal | Green LED x 8 (light up when the sensor is connected to each channel and the connection setting switch is set to ON) |
Indicators: Error | Red LED x 8 (light up when the leak liquid is detected by a sensor connected to each channel or a sensor is mounted improperly) |
Indicators: Output | Orange LED (lights up when the output relay is ON (normal)) |
Ambient Temperature | -10 to +60 ℃ +14 to +140 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ - 4 to +158 ℉ |
Ambient Humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Material | Enclosure: ABS, Unit mounting base: POM, Terminal part: PBT |
Cable | 0.2 mm2 4-core cabtyre cable, 2 m 6.562 ft long |
Cable Extension | Extension up to total less than 10 m 32.808 ft is possible, with 0.3 mm2, or more, cable. |
Weight (Typ.) | Net weight: 85 g approx. |
Accessory | SL-CP1 (Snap male connector): 8 pcs., MS-SL-2 (Unit mounting base): 1 pc. |