Head-separated Dual display Digital Pressure Sensor [For gas & liquid] DPC-L100 / DPH-L100

Single-Axis Type Digital Pressure Sensor With Optional Dual 3-Color Display

The Sensor head can be tightened with a hexagonal wrench, making installation easy especially in tight spaces. DPH / DHC-100 Pressure Sensors have a fast response time of just 500 µs. The controller automatically recognizes Sensor heads when they are connected, even if their rated pressure ranges are different. The dual display shows current and threshold values simultaneously. All these features reduce labor costs and increased productivity.

The DPH / DPC-100 Series Digital Pressure Sensors include all of the convenient features of its DP-100 Series sibling, e.g. a 3-color display, an analog output, copying function, etc.

Characteristics

  • Fast Scan Time: 500µs
  • Easy, Direct Installation In Narrow Spaces
  • Sensor Heads For Three (3) Different Pressure Ranges: Positive, Vacuum Or Compound Pressure
  • Stainless Steel Pressure Ports In Three (3) Different Shapes
  • Analog Output
  • Current And Threshold Value In One View
  • Automatic Sensor Head Recognition
  • Three Operation Modes: Easy, Hysteresis And Window Comparator Modes
  • Easy Setting
  • ECO Mode To Save Power

Part Number List

Results 9
Models table for series Head-separated Dual display Digital Pressure Sensor [For gas & liquid] DPC-L100 / DPH-L100
Part No.DatasheetCE Marking Directive ComplianceType of Pressure Rated Pressure Range Set Pressure Range Set Pressure ResolutionPressure WithstandabilityApplicable FluidDisplayDisplay: Displayable Pressure RangeSupply Voltage Power ConsumptionCurrent ConsumptionAnalog Voltage OutputResponse TimeComparative OutputComparative Output: Output OperationComparative Output: Output ModesComparative Output: HysteresisComparative Output: RepeatabilityComparative Output: Response TimeComparative Output: Short-Circuit ProtectionAnalog OutputInputs: Sensor Head Input Inputs: External InputOperation Indicator ProtectionAmbient TemperatureAmbient HumidityMedium Temperature RangeVoltage WithstandabilityInsulation Resistance Vibration ResistanceShock ResistanceTemperature Characteristics Grounding MethodPressure Port MaterialConnecting MethodCable LengthCableCable ExtensionWeight (Typ.)AccessoriesRemarkDummy
EMC Directive, RoHS Directive
Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
0 to +3.5 MPa
7 MPa
Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
20 mA or less
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉)
(including linearity, hysteresis and repeatability)
1 ms or less
IP67 (IEC)
-20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed),
Storage: -30 to +70℃ -22 to +158 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
-20 to +70 ℃ -4 to +158 ℉
150 V AC for one min. between all supply terminals connected together and enclosure
100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
1,000 m/s2 acceleration in X, Y and Z directions three times each
Capacitor earth (Enclosure-supply terminal)
R1/4 male thread (throttle embeded)
Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connector
0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Net weight : 100 g approx., Gross weight : 150 g approx.
Connector (e-CON) : 1 pc.
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
EMC Directive, RoHS Directive
Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
0 to +50 MPa
75 MPa
Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
20 mA or less
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 125 ℃ -4 to +257 ℉)
(including linearity, hysteresis and repeatability)
1 ms or less
IP67 (IEC)
-20 to +80 ℃ (Pressure port: -20 to +125 ℃
-4 to +257 ℉, No dew condensation or icing allowed),
Storage: -30 to +100 ℃ -22 to +212 ℉
[e-CON connector (accesory):
-20 to +75 ℃
-4 to +167 ℉
(Storage: -30 to +75 ℃ -22 to +167 ℉)]
35 to 85 % RH, Storage : 35 to 85 % RH
-20 to +125 ℃ -4 to +257 ℉
150 V AC for one min. between all supply terminals connected together and enclosure
100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
1,000 m/s2 acceleration in X, Y and Z directions three times each
Capacitor earth (Enclosure-supply terminal)
R1/4 male thread (throttle embeded)
Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connector
0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Net weight : 100 g approx., Gross weight : 150 g approx.
Connector (e-CON) : 1 pc.
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
Oil is used in the factory inspection process for models DPH-L114 and DPH-L154. There may be some residual oil inside the pressure port.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
EMC Directive, RoHS Directive
Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
0 to +10 MPa
20 MPa
Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
20 mA or less
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 125 ℃ -4 to +257 ℉)
(including linearity, hysteresis and repeatability)
1 ms or less
IP67 (IEC)
-20 to +80 ℃ (Pressure port: -20 to +125 ℃
-4 to +257 ℉, No dew condensation or icing allowed),
Storage: -30 to +100 ℃ -22 to +212 ℉
[e-CON connector (accesory):
-20 to +75 ℃
-4 to +167 ℉
(Storage: -30 to +75 ℃ -22 to +167 ℉)]
35 to 85 % RH, Storage : 35 to 85 % RH
-20 to +125 ℃ -4 to +257 ℉
150 V AC for one min. between all supply terminals connected together and enclosure
100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
1,000 m/s2 acceleration in X, Y and Z directions three times each
Capacitor earth (Enclosure-supply terminal)
R1/4 male thread (throttle embeded)
Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connector
0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Net weight : 100 g approx., Gross weight : 150 g approx.
Connector (e-CON) : 1 pc.
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
Oil is used in the factory inspection process for models DPH-L114 and DPH-L154. There may be some residual oil inside the pressure port.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
EMC Directive, RoHS Directive
Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
0 to +1 MPa
2 MPa
Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
20 mA or less
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉)
(including linearity, hysteresis and repeatability)
1 ms or less
IP67 (IEC)
-20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed),
Storage: -30 to +70℃ -22 to +158 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
-20 to +70 ℃ -4 to +158 ℉
150 V AC for one min. between all supply terminals connected together and enclosure
100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
1,000 m/s2 acceleration in X, Y and Z directions three times each
Capacitor earth (Enclosure-supply terminal)
R1/4 male thread (throttle embeded)
Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connector
0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Net weight : 100 g approx., Gross weight : 150 g approx.
Connector (e-CON) : 1 pc.
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
DPH-L113V : -0.1 to +1 MPa
DPH-L113 : 0 to +1 MPa
DPH-L133 : 0 to +3.5 MPa
DPH-L114 : 0 to +10 MPa
DPH-L154 : 0 to +50 MPa
(Note) : Values differ depending on a connected sensor head.
[DPH-L113V]
-1.177 to +1.177 MPa
-12.00 to +12.00 kgf/cm2
-11.77 to +11.77 bar
-170.6 to +170.6 psi
[DPH-L113]
-1.070 to +1.070 MPa
-10.91 to +10.91 kgf/cm2
-10.70 to +10.70 bar
-155.2 to +155.2 psi
[DPH-L133]
-3.74 to +3.74 MPa
-38.1 to +38.1 kgf/cm2
-37.4 to +37.4 bar
-542 to +542 psi
[DPH-L114]
-10.70 to +10.70 MPa
-109.1 to +109.1 kgf/cm2
-107.0 to +107.0 bar
-1552 to +1552 psi
[DPH-L154]
-53.5 to +53.5 MPa
-545 to +545 kgf/cm2
-535 to +535 bar
-1980 to +7760 psi
(Note) : Values differ depending on a connected sensor head.
DPH-L113V : 0.001 MPa
DPH-L113 : 0.001 MPa
DPH-L133 : 0.01 MPa
DPH-L114 : 0.01 MPa
DPH-L154 : 0.1 MPa
(Note): Values differ depending on a connected sensor head.
4 digits +4 digits 3-color LCD display
(Display refresh rate : 250 ms, 500 ms, 1,000 ms, selectable by key operation)
[DPH-L113V]
-0.155 to +1.022 MPa
-1.58 to +10.42 kgf/cm2
-1.55 to +10.22 bar
-22.4 to +148.2 psi
[DPH-L113]
-0.050 to +1.020 MPa
-0.51 to +10.40 kgf/cm2
-0.50 to +10.20 bar
-7.2 to +148.0 psi
[DPH-L133]
-0.17 to +3.57 MPa
-1.7 to +36.4 kgf/cm2
-1.7 to +35.7 bar
-24 to +518 psi
[DPH-L114]
-0.50 to +10.20 MPa
-5.1 to +104.0 kgf/cm2
-5.0 to +102.0 bar
-72 to +1480 psi
[DPH-L154]
-2.5 to +51.0 MPa
-25 to +520 kgf/cm2
-25 to +510 bar
-360 to +7400 psi
(Note): Values differ depending on a connected sensor head.
12 to 24 V DC ±10 % Ripple P-P 10 % or less
Normal operation : 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD) : 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL) : 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current

NPN open-collector transistor (2 outputs)
・ Maximum sink current : 50 mA
・ Applied voltage : 30 V DC or less
(between comparative output and 0 V)
・ Residual voltage : 1 V or less (at 50 mA sink current)
NO / NC, selectable by key operation
EASY mode / Hysteresis mode / Window comparator mode
Minimum 1 digit (variable)(however, 2 digits when using psi unit)
Within ±0.2 % F.S.
5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Incorporated

・ Output current : 1 to 5 V DC
・ Zero point : within 1 V ±0.5 % F.S. (excluding DPH-L113V) within 1.364 V ±0.5 % F.S. (DPH-L113V)
・ Span : within 4 V ±0.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Output impedance : 1 kΩ approx.


・ Output current : 4 to 20 mA
・ Zero point : within 4 mA ±1.0 % F.S. (excluding DPH-L113V) within 5.455 mA ±1.0 % F.S. (DPH-L113V)
・ Span : within 16 mA ±1.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Load resistance : 250 Ω (max.)
Input voltage range : 1 to 5 V DC (over rated pressure range)

ON voltage : 0.4 V DC or less
OFF voltage : 5 to 30 V DC, or open
Input impedance : 10 kΩ approx.
Input time : 1 ms or more
Orange LED
(Comparative output 1 operation indicator, comparative output 2 operation indicator : Lights up when each comparative output is ON )
IP40 (IEC)
-10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage : -10 to +60 ℃ +14 to +140 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
500 V AC for one min. between all supply terminals connected together and enclosure
50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
10 to 500 Hz frequency, amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each
(when panel mounting bracket is mounted : 10 to 150 Hz frequency, amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
100 m/s2 acceleration in X, Y and Z directions for three times each
Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Enclosure : PBT (glass fiber reinforced),
LCD display : Acrylic,
Mounting threaded part : Brass (nickel plated),
Switch part : Silicone rubber
Connector
Total length up to 100 m 328.1 ft (less than 30 m 98.4 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Net weight : 25 g approx. (excluding connector attached cable),
Gross weight : 140 g approx.
Pressure unit label: 1 set
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
The values specified above are applied only to the controller.
EMC Directive, RoHS Directive
DPH-L113V : -0.1 to +1 MPa
DPH-L113 : 0 to +1 MPa
DPH-L133 : 0 to +3.5 MPa
DPH-L114 : 0 to +10 MPa
DPH-L154 : 0 to +50 MPa
(Note) : Values differ depending on a connected sensor head.
[DPH-L113V]
-1.177 to +1.177 MPa
-12.00 to +12.00 kgf/cm2
-11.77 to +11.77 bar
-170.6 to +170.6 psi
[DPH-L113]
-1.070 to +1.070 MPa
-10.91 to +10.91 kgf/cm2
-10.70 to +10.70 bar
-155.2 to +155.2 psi
[DPH-L133]
-3.74 to +3.74 MPa
-38.1 to +38.1 kgf/cm2
-37.4 to +37.4 bar
-542 to +542 psi
[DPH-L114]
-10.70 to +10.70 MPa
-109.1 to +109.1 kgf/cm2
-107.0 to +107.0 bar
-1552 to +1552 psi
[DPH-L154]
-53.5 to +53.5 MPa
-545 to +545 kgf/cm2
-535 to +535 bar
-1980 to +7760 psi
(Note) : Values differ depending on a connected sensor head.
DPH-L113V : 0.001 MPa
DPH-L113 : 0.001 MPa
DPH-L133 : 0.01 MPa
DPH-L114 : 0.01 MPa
DPH-L154 : 0.1 MPa
(Note): Values differ depending on a connected sensor head.
4 digits +4 digits 3-color LCD display
(Display refresh rate : 250 ms, 500 ms, 1,000 ms, selectable by key operation)
[DPH-L113V]
-0.155 to +1.022 MPa
-1.58 to +10.42 kgf/cm2
-1.55 to +10.22 bar
-22.4 to +148.2 psi
[DPH-L113]
-0.050 to +1.020 MPa
-0.51 to +10.40 kgf/cm2
-0.50 to +10.20 bar
-7.2 to +148.0 psi
[DPH-L133]
-0.17 to +3.57 MPa
-1.7 to +36.4 kgf/cm2
-1.7 to +35.7 bar
-24 to +518 psi
[DPH-L114]
-0.50 to +10.20 MPa
-5.1 to +104.0 kgf/cm2
-5.0 to +102.0 bar
-72 to +1480 psi
[DPH-L154]
-2.5 to +51.0 MPa
-25 to +520 kgf/cm2
-25 to +510 bar
-360 to +7400 psi
(Note): Values differ depending on a connected sensor head.
12 to 24 V DC ±10 % Ripple P-P 10 % or less
Normal operation : 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD) : 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL) : 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current

PNP open-collector transistor (2 outputs)
・ Maximum source current : 50 mA
・ Applied voltage : 30 V DC or less
(between comparative output and +V)
・ Residual voltage : 1 V or less (at 50 mA source current)
NO / NC, selectable by key operation
EASY mode / Hysteresis mode / Window comparator mode
Minimum 1 digit (variable)(however, 2 digits when using psi unit)
Within ±0.2 % F.S.
5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Incorporated

・ Output current : 1 to 5 V DC
・ Zero point : within 1 V ±0.5 % F.S. (excluding DPH-L113V) within 1.364 V ±0.5 % F.S. (DPH-L113V)
・ Span : within 4 V ±0.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Output impedance : 1 kΩ approx.


・ Output current : 4 to 20 mA
・ Zero point : within 4 mA ±1.0 % F.S. (excluding DPH-L113V) within 5.455 mA ±1.0 % F.S. (DPH-L113V)
・ Span : within 16 mA ±1.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Load resistance : 250 Ω (max.)
Input voltage range : 1 to 5 V DC (over rated pressure range)

ON voltage : 5 V to +V DC
OFF voltage : 0.6 V DC or less, or open
Input impedance : 10 kΩ approx.
Input time : 1 ms or more
Orange LED
(Comparative output 1 operation indicator, comparative output 2 operation indicator : Lights up when each comparative output is ON )
IP40 (IEC)
-10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage : -10 to +60 ℃ +14 to +140 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
500 V AC for one min. between all supply terminals connected together and enclosure
50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel mounting bracket is mounted: 10 to 150 Hz frequency, double amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
100 m/s2 acceleration in X, Y and Z directions three times each
Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Enclosure : PBT (glass fiber reinforced),
LCD display : Acrylic,
Mounting threaded part : Brass (nickel plated),
Switch part : Silicone rubber
Connector
Total length up to 100 m 328.084 ft (less than 30 m 98.425 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Net weight : 25 g approx. (excluding connector attached cable),
Gross weight : 140 g approx.
CN-66A-C2 (Connector attached cable 2 m 6.562 ft), Pressure unit label: 1 set
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
The values specified above are applied only to the controller.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
EMC Directive, RoHS Directive
DPH-L113V : -0.1 to +1 MPa
DPH-L113 : 0 to +1 MPa
DPH-L133 : 0 to +3.5 MPa
DPH-L114 : 0 to +10 MPa
DPH-L154 : 0 to +50 MPa
(Note) : Values differ depending on a connected sensor head.
[DPH-L113V]
-1.177 to +1.177 MPa
-12.00 to +12.00 kgf/cm2
-11.77 to +11.77 bar
-170.6 to +170.6 psi
[DPH-L113]
-1.070 to +1.070 MPa
-10.91 to +10.91 kgf/cm2
-10.70 to +10.70 bar
-155.2 to +155.2 psi
[DPH-L133]
-3.74 to +3.74 MPa
-38.1 to +38.1 kgf/cm2
-37.4 to +37.4 bar
-542 to +542 psi
[DPH-L114]
-10.70 to +10.70 MPa
-109.1 to +109.1 kgf/cm2
-107.0 to +107.0 bar
-1552 to +1552 psi
[DPH-L154]
-53.5 to +53.5 MPa
-545 to +545 kgf/cm2
-535 to +535 bar
-1980 to +7760 psi
(Note) : Values differ depending on a connected sensor head.
DPH-L113V : 0.001 MPa
DPH-L113 : 0.001 MPa
DPH-L133 : 0.01 MPa
DPH-L114 : 0.01 MPa
DPH-L154 : 0.1 MPa
(Note): Values differ depending on a connected sensor head.
4 digits +4 digits 3-color LCD display
(Display refresh rate : 250 ms, 500 ms, 1,000 ms, selectable by key operation)
[DPH-L113V]
-0.155 to +1.022 MPa
-1.58 to +10.42 kgf/cm2
-1.55 to +10.22 bar
-22.4 to +148.2 psi
[DPH-L113]
-0.050 to +1.020 MPa
-0.51 to +10.40 kgf/cm2
-0.50 to +10.20 bar
-7.2 to +148.0 psi
[DPH-L133]
-0.17 to +3.57 MPa
-1.7 to +36.4 kgf/cm2
-1.7 to +35.7 bar
-24 to +518 psi
[DPH-L114]
-0.50 to +10.20 MPa
-5.1 to +104.0 kgf/cm2
-5.0 to +102.0 bar
-72 to +1480 psi
[DPH-L154]
-2.5 to +51.0 MPa
-25 to +520 kgf/cm2
-25 to +510 bar
-360 to +7400 psi
(Note): Values differ depending on a connected sensor head.
12 to 24 V DC ±10 % Ripple P-P 10 % or less
Normal operation : 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD) : 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL) : 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current

NPN open-collector transistor (2 outputs)
・ Maximum sink current : 50 mA
・ Applied voltage : 30 V DC or less
(between comparative output and 0 V)
・ Residual voltage : 1 V or less (at 50 mA sink current)
NO / NC, selectable by key operation
EASY mode / Hysteresis mode / Window comparator mode
Minimum 1 digit (variable)(however, 2 digits when using psi unit)
Within ±0.2 % F.S.
5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Incorporated

・ Output current : 1 to 5 V DC
・ Zero point : within 1 V ±0.5 % F.S. (excluding DPH-L113V) within 1.364 V ±0.5 % F.S. (DPH-L113V)
・ Span : within 4 V ±0.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Output impedance : 1 kΩ approx.


・ Output current : 4 to 20 mA
・ Zero point : within 4 mA ±1.0 % F.S. (excluding DPH-L113V) within 5.455 mA ±1.0 % F.S. (DPH-L113V)
・ Span : within 16 mA ±1.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Load resistance : 250 Ω (max.)
Input voltage range : 1 to 5 V DC (over rated pressure range)

ON voltage : 0.4 V DC or less
OFF voltage : 5 to 30 V DC, or open
Input impedance : 10 kΩ approx.
Input time : 1 ms or more
Orange LED
(Comparative output 1 operation indicator, comparative output 2 operation indicator : Lights up when each comparative output is ON )
IP40 (IEC)
-10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage : -10 to +60 ℃ +14 to +140 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
500 V AC for one min. between all supply terminals connected together and enclosure
50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
10 to 500 Hz frequency, double amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each (when panel mounting bracket is mounted: 10 to 150 Hz frequency, double amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
100 m/s2 acceleration in X, Y and Z directions three times each
Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Enclosure : PBT (glass fiber reinforced),
LCD display : Acrylic,
Mounting threaded part : Brass (nickel plated),
Switch part : Silicone rubber
Connector
Total length up to 100 m 328.084 ft (less than 30 m 98.425 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Net weight : 25 g approx. (excluding connector attached cable),
Gross weight : 140 g approx.
CN-66A-C2 (Connector attached cable 2 m 6.562 ft), Pressure unit label: 1 set
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
The values specified above are applied only to the controller.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
EMC Directive, RoHS Directive
Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
-0.1 to +1 MPa
2 MPa
Gases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
20 mA or less
Output voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉)
(including linearity, hysteresis and repeatability)
1 ms or less
IP67 (IEC)
-20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed),
Storage: -30 to +70℃ -22 to +158 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
-20 to +70 ℃ -4 to +158 ℉
150 V AC for one min. between all supply terminals connected together and enclosure
100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
1,000 m/s2 acceleration in X, Y and Z directions three times each
Capacitor earth (Enclosure-supply terminal)
R1/4 male thread (throttle embeded)
Diaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connector
0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Extension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Net weight : 100 g approx., Gross weight : 150 g approx.
Connector (e-CON) : 1 pc.
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)
DPH-L113V : -0.1 to +1 MPa
DPH-L113 : 0 to +1 MPa
DPH-L133 : 0 to +3.5 MPa
DPH-L114 : 0 to +10 MPa
DPH-L154 : 0 to +50 MPa
(Note) : Values differ depending on a connected sensor head.
[DPH-L113V]
-1.177 to +1.177 MPa
-12.00 to +12.00 kgf/cm2
-11.77 to +11.77 bar
-170.6 to +170.6 psi
[DPH-L113]
-1.070 to +1.070 MPa
-10.91 to +10.91 kgf/cm2
-10.70 to +10.70 bar
-155.2 to +155.2 psi
[DPH-L133]
-3.74 to +3.74 MPa
-38.1 to +38.1 kgf/cm2
-37.4 to +37.4 bar
-542 to +542 psi
[DPH-L114]
-10.70 to +10.70 MPa
-109.1 to +109.1 kgf/cm2
-107.0 to +107.0 bar
-1552 to +1552 psi
[DPH-L154]
-53.5 to +53.5 MPa
-545 to +545 kgf/cm2
-535 to +535 bar
-1980 to +7760 psi
(Note) : Values differ depending on a connected sensor head.
DPH-L113V : 0.001 MPa
DPH-L113 : 0.001 MPa
DPH-L133 : 0.01 MPa
DPH-L114 : 0.01 MPa
DPH-L154 : 0.1 MPa
(Note): Values differ depending on a connected sensor head.
4 digits +4 digits 3-color LCD display
(Display refresh rate : 250 ms, 500 ms, 1,000 ms, selectable by key operation)
[DPH-L113V]
-0.155 to +1.022 MPa
-1.58 to +10.42 kgf/cm2
-1.55 to +10.22 bar
-22.4 to +148.2 psi
[DPH-L113]
-0.050 to +1.020 MPa
-0.51 to +10.40 kgf/cm2
-0.50 to +10.20 bar
-7.2 to +148.0 psi
[DPH-L133]
-0.17 to +3.57 MPa
-1.7 to +36.4 kgf/cm2
-1.7 to +35.7 bar
-24 to +518 psi
[DPH-L114]
-0.50 to +10.20 MPa
-5.1 to +104.0 kgf/cm2
-5.0 to +102.0 bar
-72 to +1480 psi
[DPH-L154]
-2.5 to +51.0 MPa
-25 to +520 kgf/cm2
-25 to +510 bar
-360 to +7400 psi
(Note): Values differ depending on a connected sensor head.
12 to 24 V DC ±10 % Ripple P-P 10 % or less
Normal operation : 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage)
ECO mode (STD) : 720 mW or less (Current consumption 30 mA or less at 24 V supply voltage)
ECO mode (FULL) : 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage)
Excluding the current consumption of sensor head and analog output current

PNP open-collector transistor (2 outputs)
・ Maximum source current : 50 mA
・ Applied voltage : 30 V DC or less
(between comparative output and +V)
・ Residual voltage : 1 V or less (at 50 mA source current)
NO / NC, selectable by key operation
EASY mode / Hysteresis mode / Window comparator mode
Minimum 1 digit (variable)(however, 2 digits when using psi unit)
Within ±0.2 % F.S.
5 ms, 10 ms, 25 ms, 50 ms, 100 ms, 250 ms, 500 ms, 1,000 ms, 5,000 ms, selectable by key operation
Incorporated

・ Output current : 1 to 5 V DC
・ Zero point : within 1 V ±0.5 % F.S. (excluding DPH-L113V) within 1.364 V ±0.5 % F.S. (DPH-L113V)
・ Span : within 4 V ±0.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Output impedance : 1 kΩ approx.


・ Output current : 4 to 20 mA
・ Zero point : within 4 mA ±1.0 % F.S. (excluding DPH-L113V) within 5.455 mA ±1.0 % F.S. (DPH-L113V)
・ Span : within 16 mA ±1.5 % F.S.
・ Linearity : within ±0.1 % F.S.
・ Load resistance : 250 Ω (max.)
Input voltage range : 1 to 5 V DC (over rated pressure range)

ON voltage : 5 V to +V DC
OFF voltage : 0.6 V DC or less, or open
Input impedance : 10 kΩ approx.
Input time : 1 ms or more
Orange LED
(Comparative output 1 operation indicator, comparative output 2 operation indicator : Lights up when each comparative output is ON )
IP40 (IEC)
-10 to +50 ℃ +14 to +122 ℉ (No dew condensation or icing allowed), Storage : -10 to +60 ℃ +14 to +140 ℉
35 to 85 % RH, Storage : 35 to 85 % RH
500 V AC for one min. between all supply terminals connected together and enclosure
50 MΩ, or more, with 500 V DC megger between all supply terminals connected together and enclosure
10 to 500 Hz frequency, amplitude 3 mm 0.118 in or maximum acceleration 196 m/s2, in X, Y and Z directions for two hours each
(when panel mounting bracket is mounted : 10 to 150 Hz frequency, amplitude 0.75 mm 0.030 in or maximum acceleration 49 m/s2, in X, Y and Z directions for two hours each)
100 m/s2 acceleration in X, Y and Z directions for three times each
Within ±0.5 % F.S. (ambient temperature range based on +20 ℃ +68 ℉)
Enclosure : PBT (glass fiber reinforced),
LCD display : Acrylic,
Mounting threaded part : Brass (nickel plated),
Switch part : Silicone rubber
Connector
Total length up to 100 m 328.1 ft (less than 30 m 98.4 ft when conforming to CE marking) is possible with 0.3 mm2, or more, cable.
Net weight : 25 g approx. (excluding connector attached cable),
Gross weight : 140 g approx.
Pressure unit label: 1 set
Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20 ℃ +68 ℉.
The values specified above are applied only to the controller.