Specification

Specifications table for model DPH-L113
ItemPerformance characteristics
CE Marking Directive ComplianceEMC Directive, RoHS Directive
Type of Pressure Sealed gauge pressure
(Note): The sensor's internal mechanism is sealed based on an air pressure of 1,013 hPa.
Rated Pressure Range 0 to +1 MPa
Pressure Withstandability2 MPa
Applicable FluidGases and fluids that do not corrode stainless steel SUS630, SUS304, or SUSXM7
Supply Voltage 9 to 36 V DC
[9 to 32 V DC when using the attached connector (e-CON)]
Current Consumption20 mA or less
Analog Voltage OutputOutput voltage: 1 to 5 V DC (over rated pressure range)
Accuracy: ±1.0 % F.S. (at 23 ±2 ℃ +73.4 ±35 ℉)
±2.0 % F.S. (at -20 to 70 ℃ -4 to +158 ℉)
(including linearity, hysteresis and repeatability)
Response Time1 ms or less
ProtectionIP67 (IEC)
Ambient Temperature-20 to +70 ℃ -4 to +158 ℉ (No dew condensation or icing allowed),
Storage: -30 to +70℃ -22 to +158 ℉
Ambient Humidity35 to 85 % RH, Storage : 35 to 85 % RH
Medium Temperature Range-20 to +70 ℃ -4 to +158 ℉
Voltage Withstandability150 V AC for one min. between all supply terminals connected together and enclosure
Insulation Resistance100 MΩ, or more, with 50 V DC megger between all supply terminals connected together and enclosure
Vibration Resistance10 to 2,000 Hz frequency, acceleration 200 m/s2, in X direction for four hours, in Y and Z directions for two hours each
(Note): The X, Y, and Z directions are defined as follows :
Shock Resistance1,000 m/s2 acceleration in X, Y and Z directions three times each
Grounding MethodCapacitor earth (Enclosure-supply terminal)
Pressure Port R1/4 male thread (throttle embeded)
MaterialDiaphragm : Stainless steel (SUS603), Pressure port : Stainless steel (SUS304), Throttle : Stainless steel (SUSXM7)
Connecting MethodConnector
Cable0.2 mm2 3-core heat resistant cabtyre cable 2 m 3.562 ft long
Cable ExtensionExtension up to total 10 m 32.808 ft is possible with 0.2 mm2, or more, cable.
Weight (Typ.)Net weight : 100 g approx., Gross weight : 150 g approx.
AccessoriesConnector (e-CON) : 1 pc.
RemarkWhere measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23 ℃ +73.4 ℉.
The sensor head can be used independently.
DummyCE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations)