Item | Performance characteristics |
---|---|
CE Marking Directive Compliance | EMC Directive (Note), RoHS Directive (Note): If our product will be incorporated in a customer product that will comply with the EMC Directive, install our product in a conductive box in accordance with "PLC User's Manual [Published by Mitsubishi Electric Corporation]". |
Compatible Controllers | HG-SCâ–¡ / HG-TCâ–¡ |
Number of Connectable Units | Maximum of 15 controllers (one master, 14 slaves) per SC-HG1-C unit |
Supply Voltage | 24 V DC ±10 %, including ripple 0.5 V (P-P) (Note): Power is supplied from a connected controller / master controller. |
Current Consumption | 80 mA or less |
Communication Method | Switchable CC-Link Ver.1.10 or 2.00 |
Remote Station Type | Remote device station |
Number of Occupied Station | CC-Link Ver.1.10 : 4 stations, CC-Link Ver.2.00 : Switchable 2 or 4 stations |
Station No. Setting | 1 to 64 (0 and 65 or more : Error) |
Baud Rate / Maximum Overall Cable Distance | ・10 Mbps/100 m 328.084 ft ・5 Mbps/160 m 524.934 ft ・2.5 Mbps/400 m 1,312.336 ft ・625 kbps/900 m 2,952.756 ft ・156 kbps/1,200 m 3,937.008 ft |
Degree of Pollution | 2 |
Operating Altitude | 2,000 m 6561.68 ft or less (Note): Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m. |
Environmental Resistance: Protection | IP40 (IEC) |
Environmental Resistance: Ambient Temperature | -10 to +45 ℃ +14 to +113 ℉ (No condensation or icing), Storage : -20 to +60 ℃ -4 to +140 ℉ |
Environmental Resistance: Ambient Humidity | 35 to 85 % RH, Storage : 35 to 85 % RH |
Voltage Withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
Insulation Resistance | 20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure |
Environmental Resistance: Vibration Resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each |
Environmental Resistance: Shock Resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each |
Material | Unit case : Polycarbonate |
Communication Cable | Specified cable (shielded twisted cable) (Note): Use only a special-use communication cable that is approved by the CC-Link Partner Association. |
Weight (Typ.) | Net weight : 80 g approx., Gross weight : 130 g approx. |
Remark | Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20 ℃ +68 ℉. |