Specification

Specifications table for model SC-HG1-C
ItemPerformance characteristics
CE Marking Directive ComplianceEMC Directive (Note), RoHS Directive
(Note): If our product will be incorporated in a customer product that will comply with the EMC Directive, install our product in a conductive box in accordance with "PLC User's Manual [Published by Mitsubishi Electric Corporation]".
Compatible ControllersHG-SCâ–¡ / HG-TCâ–¡
Number of Connectable UnitsMaximum of 15 controllers (one master, 14 slaves) per SC-HG1-C unit
Supply Voltage 24 V DC ±10 %, including ripple 0.5 V (P-P)
(Note): Power is supplied from a connected controller / master controller.
Current Consumption80 mA or less
Communication MethodSwitchable CC-Link Ver.1.10 or 2.00
Remote Station TypeRemote device station
Number of Occupied StationCC-Link Ver.1.10 : 4 stations, CC-Link Ver.2.00 : Switchable 2 or 4 stations
Station No. Setting1 to 64 (0 and 65 or more : Error)
Baud Rate / Maximum Overall Cable Distance・10 Mbps/100 m 328.084 ft
・5 Mbps/160 m 524.934 ft
・2.5 Mbps/400 m 1,312.336 ft
・625 kbps/900 m 2,952.756 ft
・156 kbps/1,200 m 3,937.008 ft
Degree of Pollution2
Operating Altitude2,000 m 6561.68 ft or less
(Note): Do not use or store in an environment that has been pressurized to an air pressure higher than the atmospheric pressure at 0 m.
Environmental Resistance: ProtectionIP40 (IEC)
Environmental Resistance: Ambient Temperature-10 to +45 ℃ +14 to +113 ℉ (No condensation or icing), Storage : -20 to +60 ℃ -4 to +140 ℉
Environmental Resistance: Ambient Humidity35 to 85 % RH, Storage : 35 to 85 % RH
Voltage Withstandability1,000 V AC for one min. between all supply terminals connected together and enclosure
Insulation Resistance20 MΩ or more, with 250 V DC megger between all supply terminals connected together and enclosure
Environmental Resistance: Vibration Resistance10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 to 58Hz), maximum acceleration 49 m/s2 (58 to 150 Hz) in X, Y and Z directions for two hours each
Environmental Resistance: Shock Resistance98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each
MaterialUnit case : Polycarbonate
Communication CableSpecified cable (shielded twisted cable)
(Note): Use only a special-use communication cable that is approved by the CC-Link Partner Association.
Weight (Typ.)Net weight : 80 g approx., Gross weight : 130 g approx.
RemarkWhere measurement conditions have not been specified precisely, the conditions used were ambient temperature +20 ℃ +68 ℉.

Stock Check

What's New