Specification

Specifications table for model EX-F61
ItemPerformance characteristics
Sensing Object Agent, such as Sulfuric acid, Hydrochloric acid, Phosphoric acid or Ammonia etc.
Note : Highly viscous liquid may not be detected stably.
Note : The agents mentioned above are examples. For details, please contact our office.
Note : PVC mounting bracket may not be used depending on type or viscosity etc. of the agent. For details, please contact our office.
Supply Voltage 12 to 24 V DC ± 10 % Ripple P-P 10 % or less
Current Consumption15 mA or less
OutputNPN open-collector transistor
- Maximum sink current: 50 mA
- Applied voltage: 30 V DC or less (between output and 0 V)
- Residual voltage: 1.0 V or less (at 50 mA sink current), 0.4 V or less (at 16 mA sink current)
Output: Output Operation In normal state: ON, When leak detected or the sensor is mounted improperly: OFF
Output: Short-Circuit ProtectionIncorporated
Response Time50 ms or less
Fault IndicatorRed LED (lights up when the leak liquid is detected, or the sensor is mounted improperly)
Normal IndicatorGreen LED (lights up when the sensor is mounted properly)
ProtectionIP67 (IEC)
Ambient Temperature-10 to +60 ℃ +14 to +140 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ - 4 to +158 ℉
Note : Liquid being detected should also be kept within the rated ambient temperature range.
Ambient Humidity35 to 85 % RH, Storage: 35 to 85 % RH
Ambient IlluminanceIncandescent light: 1,000 ℓx or less at the light-receiving face
Emitting ElementInfrared LED (non-modulated)
MaterialEnclosure: PFA
Cable0.1 mm2 3-core PFA cabtyre cable, 3 m 9.843 ft long
Cable ExtensionExtension up to total 50 m 164.042 ft is possible with 0.3 mm2, or more, cable.
Weight (Typ.)Net weight: 60 g approx.
AccessoryMS-EX-F6-1(PFA mounting bracket): 1 pc.