Item | Performance characteristics |
---|---|
Memory Capacity: Memory Selection Pattern 1 | Program (steps)(Note) : 64,000 Data register (words)(Note) : 131,072 Number of max. program block (PB) : 128 (Note) The factory default setting is pattern 1. (Note) For data register (DT), data up to 262,144 words can be backed up. |
Memory Capacity: Memory Selection Pattern 2 | Program (steps)(Note) : 32,000 Data register (words)(Note) : 262,144 Number of max. program block (PB) : 64 (Note1) For data register (DT), data up to 262,144 words can be backed up. |
Programming Method | Relay symbol method |
Method | Cyclic operation method |
Program Memory | Built-in flash ROM (no backup battery required) |
Operation Speed | Basic instruction: min. 14 ns/step |
External Input (X) | 8,192 points (Note) Hardware configuration governs the actually usable number of I/O points. When I/O points are not actually used, usable as internal relays. |
External Output (Y) | 8,192 points (Note) Hardware configuration governs the actually usable number of I/O points. When I/O points are not actually used, usable as internal relays. |
Internal Relay (R) | 32,768 points |
System Relay (SR) | Indicate operation status of various relays is shown. |
Link Relay (L) | 16,384 points |
Timer (T) | 4,096 points: Timer capable of counting (units: 10 μs, 1 ms, 10 ms, 100 ms or 1 sec.) x 4,294,967,295 |
Counter (C) (C) | 1,024 points, Counter capable of counting 1 to 4,294,967,295 |
Link Data Register (LD) | 16,384 words |
System Data Register (SD) | Internal operation status of various registers is shown. |
Index Register (I0 to IE) | 15 long words / With switching function |
Master Control Relay (MCR) | Unlimited |
Number of Labels (LOOP) | Max. 65,535 points for each program block (PB) |
Differential Points | Unlimited |
Number of Step Ladders | Unlimited |
Number of Subroutines | Max. 65,535 points for each program block (PB) |
Number of Interrupt Program | 1 periodical interrupt program |
Real Time Clock | Year (last two digits), month, day, hours (24-hour display) minutes, seconds, day of week (Note)Precision of calendar; At 0 ℃ +32 ℉, 95 sec. or less error per month, at +25 ℃ +77 ℉, 15 sec. or less error per month, at +55 ℃ +131 ℉, 130 sec. or less error per month |
PLC Link Function | Max. 16 units, link relays: 1,024 points, link registers: 128 words. (Data transfer and remote programming are not supported) (Link area allocation is switchable between the first and the second half) |
Interface | RS-232C, three-wire system, 1 channel (Note) SD, RD and SG terminals are isolated from internal circuits. |
Transmission Distance | 15 m 49.213 ft |
Transmission Speed | 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200, 230,400 bits/sec, |
Communication Method | Half-duplex system |
Synchronous Method | Start-stop synchronization system |
Transmission Format | Stop bit: 1 bit / 2 bits Parity: none / odd / even Data length: 7 bits / 8 bits Start code: with STX / without STX End code: CR / CR + LF / none / ETX |
Data Transmission Order | Transmit from bit 0 in character units. |
:5V | For 5 V DC type GT series Programmable Display |
Ambient Temperature | 0 to +55 ℃ +32 to +131 ℉, Storage: -40 to +70 ℃ -40 to +158 ℉ |
Ambient Humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation) |
Breakdown Voltage | 500 V AC for 1 minute |
Insulation Resistance | 100 MΩ or more (at 500 V DC) |
Vibration Resistance | 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in, 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions |
Noise Immunity | 1,000 V [p-p] with pulse width 50 ns and 1 μs (using a noise simulator) |
Shock Resistance | 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2) |
Operating Condition | Free from corrosive gasses and excessive dust |
Rated Voltage Range | 20.4 to 28.8 V DC |
Current Consumption | 150 mA or less |
Net Weight | 180 g approx. (with terminal block and end unit) |
The service is owned, operated, controlled and managed by Panasonic's distributors.
For pricing, delivery and technical questions related to this service, please direct to them.
Panasonic assumes no responsibility for any dealings you may have with distributors.